配電變壓器的電壓調節方法及影響

電(dian)(dian)壓合格率(lv)(lv)是衡量(liang)(liang)電(dian)(dian)能質量(liang)(liang)的主要(yao)指標之(zhi)(zhi)一。可是由于種種原因,高(gao)峰和(he)(he)低(di)谷(gu)時期的用電(dian)(dian)量(liang)(liang)往(wang)往(wang)相差懸殊,造成配(pei)電(dian)(dian)變(bian)壓器(qi)輸出電(dian)(dian)壓忽(hu)高(gao)忽(hu)低(di)。而電(dian)(dian)壓的忽(hu)高(gao)忽(hu)低(di)對各種用電(dian)(dian)設(she)備的性能、生產效(xiao)率(lv)(lv)和(he)(he)產品(pin)質量(liang)(liang)都有不(bu)同(tong)程度(du)的影響,因此,為了確保供電(dian)(dian)電(dian)(dian)壓的合格率(lv)(lv),及時調(diao)節配(pei)電(dian)(dian)變(bian)壓器(qi)分(fen)接開關位置是解(jie)決問題的辦法之(zhi)(zhi)一。

一般配電(dian)變(bian)壓器(qi)大多(duo)屬于(yu)無載調壓,共有3個擋位(wei)可供調節。通過改變(bian)分接(jie)開關動觸頭的位(wei)置來(lai)改變(bian)變(bian)壓器(qi)繞組的匝數,從(cong)而改變(bian)輸出電(dian)壓。常用配電(dian)變(bian)壓器(qi)一次電(dian)壓為(wei)(wei)10千伏(fu),二次輸出電(dian)壓為(wei)(wei)0.4千伏(fu)。配電(dian)變(bian)壓器(qi)分接(jie)開關的Ⅰ擋位(wei)置為(wei)(wei)10.5千伏(fu),Ⅱ擋位(wei)置為(wei)(wei)10千伏(fu),Ⅲ擋位(wei)置為(wei)(wei)9.5千伏(fu),一般應在Ⅱ擋位(wei)置。

調(diao)節(jie)分接開關(guan)的具體(ti)步驟為:

1.先停電。斷開(kai)配(pei)電變壓(ya)器低壓(ya)側(ce)負(fu)荷后(hou),用絕緣棒拉開(kai)高壓(ya)側(ce)跌落式熔斷器,然后(hou)做好必要的安全(quan)措(cuo)施。擰開(kai)變壓(ya)器上的分接開(kai)關保護蓋(gai),將定位銷置(zhi)于空擋(dang)位置(zhi)。

2.調(diao)節(jie)擋位(wei)時,應(ying)根據輸出電(dian)壓高(gao)低(di),調(diao)節(jie)分接開關到相應(ying)位(wei)置,調(diao)節(jie)分接開關的基本原則是:

當(dang)變壓器輸出(chu)電壓低于允(yun)許(xu)值時,把分接(jie)開關位置由(you)Ⅰ擋(dang)調到Ⅱ擋(dang),或由(you)Ⅱ擋(dang)調整到Ⅲ擋(dang);

當變壓器輸出電壓高(gao)于允許值時,把分接(jie)開關位(wei)置由Ⅲ擋(dang)調(diao)到(dao)Ⅱ擋(dang),或Ⅱ擋(dang)調(diao)整(zheng)到(dao)Ⅰ擋(dang)。

3.調節擋位后,用直(zhi)流電(dian)橋測量各相(xiang)繞(rao)組直(zhi)流電(dian)阻值,檢查(cha)各繞(rao)組之(zhi)間直(zhi)流電(dian)阻是否(fou)平衡(heng)。若各相(xiang)之(zhi)間電(dian)阻值相(xiang)差大于(yu)2%,須重新調整,否(fou)則運行(xing)后,動靜觸(chu)頭會(hui)因接(jie)觸(chu)不(bu)好(hao)而(er)發熱甚至放電(dian),損壞變壓(ya)器。